KFD0-CS-EX1.54 现货直发 安全栅
型号:
KFD0-CS-EX1.54
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Rated voltage | loop powered | |
| Power dissipation | < 0.2 W for Uin = 24 V, Iout = 20 mA | |
| Control circuit | ||
| Connection | terminals 11+, 12- | |
| Voltage | 0 ... 24 V | |
| Current | 0 ... 20 mA , I < 35 mA | |
| Field circuit | ||
| Connection | terminals 1+, 2- | |
| Voltage | for 4 V ≤ Uin ≤ 24 V: Uout ≥ Uin - (0.41 x Iin in mA) - 0.5 | |
| Short-circuit current | ≤ 35 mA | |
| Transmission range | voltage: 4 ... 20 V DC/0 ... 6 Vpp AC current: 1 ... 20 mA | |
| Transfer characteristics | ||
| Deviation | ||
| After calibration | ≤ 3.5 mA current loss at 20 mA load current | |
| Influence of ambient temperature | ± 20 µA / K | |
| Rise time/fall time | ≤ 50 µs (load current ≥ 1 mA) | |
| Galvanic isolation | ||
| Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Indicators/settings | ||
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Protection against electrical shock | UL 61010-1 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |